Medium voltage power cable / XLPE
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  Single Conductor XLPE 5 kV 133% I.L.
  Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial.

Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639 - UL 1072

  Electrical Data
 

 

 

 

Continuous operating temperature

 

90º C

Maximum Operating voltage

 

5000 V

Test voltage

 

23 kV ac x 5min

Partial discharge at test voltage

 

< 5 pC



 

 

Download Document:

 
  Data of Cable  


 

Conductor
Size
(AWG / kcmil)
Stranded Conductor
Thickness
(mils)
Aprox. weight
(Pounds/kft)
Overall Diam. (inch)
Ampacities
Section (MCM)
Number of Wires
Diameter (inch)
Direct. Burial
In Duct
In Air
Wires
Strand
Insulat.
Jacket
Cu
Al
Cu
Al
Cu
Al
Cu
Al
8
17
7
0.049
0.146
90
60
191
155
0.589
109
85
78
61
97
76
6
26
7
0.061
0.183
90
60
235
179
0.626
139
108
101
78
128
99
4
42
7
0.077
0.231
90
60
303
213
0.675
179
140
130
101
168
131
2
66
7
0.097
0.292
90
60
404
262
0.736
230
180
168
131
221
173
2
66
19
0.059
0.287
90
60
401
258
0.730
230
180
168
131
221
173
1
84
19
0.067
0.323
90
60
470
289
0.766
276
205
193
150
265
200
1/0
106
19
0.074
0.362
90
60
552
326
0.805
297
233
218
171
296
232
2/0
133
19
0.084
0.407
90
80
680
393
0.890
337
264
248
195
341
267
3/0
168
19
0.094
0.457
90
80
810
448
0.939
377
296
283
222
390
306
4/0
212
19
0.106
0.512
90
80
969
514
0.994
426
336
312
253
450
354
250
250
37
0.082
0.559
90
80
1112
574
1.041
457
365
346
277
492
393
300
300
37
0.090
0.612
90
80
1293
647
1.094
501
403
381
307
548
440
350
350
37
0.097
0.661
90
80
1469
717
1.144
541
437
414
335
601
485
500
500
37
0.116
0.789
90
80
2011
939
1.287
645
527
499
408
743
605
750
750
61
0.111
0.970
90
80
2892
1276
1.469
782
650
615
512
945
782
1000
1000
61
0.128
1.118
90
80
3759
1612
1.632
888
751
706
598
1109
933

 

Options :

  1. External cover of PVC
  2. “Sun light Resistant” - “Cable Tray Use”
  3. Screen of Concentric Wires

The provided values are approximated and subject to changes without previous warning.

 