Medium voltage power cable / XLPE
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  Single Conductor XLPE 15 kV 133% I.L.
  Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial.

Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639 - UL 1072

  Electrical Data
 

 

 

 

Continuous operating temperature

 

90º C

Maximum Operating voltage

 

15000 V

Test voltage 1000 kcmil:

 

35 kV ac x 5min

Test voltage 1000 kcmil:   44 kV ac x 5min

Partial discharge at test voltage

 

< 5 pC



 

 

 

Download Document:

 
  Data of Cable  


 

Conductor
Size
(AWG / MCM)
Stranded Conductor
Thickness
(mils)
Aprox. weight
(Pounds/kft)
Overall Diam. (inch)
Ampacities
Section (MCM)
Number of Wires
Diameter (inch)
Direct. Burial
In Duct
In Air
Wires
Strand
Insulat.
Jacket
Cu
Al
Cu
Al
Cu
Al
Cu
Al
2
66
7
0.097
0.292
220
80
590
448
1.035
220
171
170
134
223
174
2
66
19
0.059
0.287
220
80
586
444
1.030
226
175
172
135
225
176
1
84
19
0.067
0.323
220
80
662
481
1.065
248
195
196
154
258
202
1/0
106
19
0.074
0.362
220
80
751
525
1.104
282
222
223
175
297
233
2/0
133
19
0.084
0.407
220
80
867
579
1.150
320
252
253
199
341
268
3/0
168
19
0.094
0.457
220
80
1004
642
1.199
362
286
286
227
391
308
4/0
212
19
0.106
0.512
220
80
1188
734
1.270
409
325
325
258
449
355
250
250
37
0.082
0.559
220
80
1340
802
1.317
448
356
356
284
498
395
300
300
37
0.090
0.612
220
80
1530
884
1.370
492
393
392
314
555
441
350
350
37
0.097
0.661
220
80
1715
964
1.419
533
427
426
342
608
485
500
500
37
0.116
0.789
220
80
2263
1190
1.547
637
516
513
416
749
604
750
750
61
0.111
0.970
220
110
3241
1625
1.789
769
633
629
519
937
767
1000
1000
61
0.128
1.118
220
110
4166
2019
1.969
876
733
722
606
1099
913
1250
1250
91
0.117
1.252
220
110
5060
2368
2.102
920
822
754
672
1155
1022
1500
1500
91
0.128
1.370
220
110
5921
2699
2.220
949
875
777
717
1190
1090

 

Options :

  1. External cover of PVC
  2. “Sun light Resistant” - “Cable Tray Use”
  3. Screen of Concentric Wires

The provided values are approximated and subject to changes without previous warning.

 

  HOME THE COMPANY PRODUCTS TECHNICAL INFORMATION CONTACT US REPRESENTATIVES
2005 © Electroconductores, C.A. All rights reserved.