Single Conductor XLPE 115 kV |
 |
| |
Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial. |
|
 |
| |
Electrical Data |
 |
| |
|
|
|
Continuous operating temperature |
|
90º C |
Maximum Operating voltage |
|
115000 V |
|
|
|
Download Document:
|
| |
|
| |
Data of Cable |
|
 |
|
Conduct |
Stranded Conductor |
Thickness
(mils) |
Aprox. weight
(Pounds/kft) |
Overl Diam. (inch) |
Ampacities
(Cu) |
Size |
Section (MCM) |
Numb of
Wires |
Diameter (inch) |
Direct Burial |
In
Duct |
In
Air |
(AWG / MCM) |
Wires |
Strand |
Insulat. |
Jacket |
Cu |
Al |
750 |
750 |
61 |
0.111 |
0.970 |
799 |
140 |
5474 |
3858 |
3.087 |
746 |
652 |
908 |
1000 |
1000 |
61 |
0.128 |
1.118 |
799 |
140 |
6501 |
4354 |
3.250 |
857 |
749 |
1068 |
1250 |
1250 |
91 |
0.117 |
1.252 |
799 |
140 |
7486 |
4794 |
3.384 |
888 |
786 |
1141 |
1500 |
1500 |
91 |
0.128 |
1.370 |
799 |
140 |
8431 |
5208 |
3.502 |
917 |
805 |
1172 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Options : |
- External cover of PVC
- “Sun light Resistant” - “Cable Tray Use”
- Screen of Concentric Wires
|
The provided values are approximated and subject to changes without previous warning.
|
|