Medium voltage power cable / EPR
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  Single Conductor EPR 5 kV 133% I.L.
  Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial.

Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639

  Electrical Data
 

 

 

 

Continuous operating temperature

 

90º C

Maximum Operating voltage

 

5000 V

Test voltage

 

23 kV ac x 5min

Partial discharge at test voltage

 

< 5 pC



 

 

Download Document:

 
  Data of Cable  


 


Conductor
Size
(AWG / MCM)

Stranded Conductor

Thickness
(mils)

Aprox. weight
(Pounds/kft)

Overall Diam. (inch)

Ampacities

Section (MCM)

Number of Wires

Diameter (inch)

Direct. Burial

In Duct

In Air

Wires

Strand

Insulat.

Jacket

Cu

Al

Cu

Al

Cu

Al

Cu

Al

8

17

7

0.049

0.146

115

60

229

194

0.640

109

85

78

61

97

76

6

26

7

0.061

0.183

115

60

276

220

0.677

139

108

101

78

128

99

4

42

7

0.077

0.231

115

60

348

258

0.726

179

140

130

101

168

131

2

66

7

0.097

0.292

115

60

454

311

0.787

230

180

168

131

221

173

2

66

19

0.059

0.287

115

60

450

307

0.781

230

180

168

131

221

173

1

84

19

0.067

0.323

115

60

522

342

0.817

276

205

193

150

265

200

1/0

106

19

0.074

0.362

115

80

629

403

0.896

297

233

218

171

296

232

2/0

133

19

0.084

0.407

115

80

740

453

0.941

337

264

248

195

341

267

3/0

168

19

0.094

0.457

115

80

873

512

0.990

377

296

283

222

390

306

4/0

212

19

0.106

0.512

115

80

1037

582

1.045

426

336

312

253

450

354

250

250

37

0.082

0.559

115

80

1184

646

1.093

457

365

346

277

492

393

300

300

37

0.090

0.612

115

80

1369

722

1.146

501

403

381

307

548

440

350

350

37

0.097

0.661

115

80

1549

797

1.195

541

437

414

335

601

485

500

500

37

0.116

0.789

115

80

2101

1029

1.339

645

527

499

408

743

605

750

750

61

0.111

0.970

115

80

2996

1380

1.520

782

650

615

512

945

782

1000

1000

61

0.128

1.118

115

110

3942

1795

1.744

888

751

706

598

1109

933

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 


Options :

  1. External cover of PVC
  2. “Sun light Resistant” - “Cable Tray Use”
  3. Screen of Concentric Wires

 

The provided values are approximated and subject to changes without previous warning.

  HOME THE COMPANY PRODUCTS TECHNICAL INFORMATION CONTACT US REPRESENTATIVES