Medium voltage power cable / EPR
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  Single Conductor EPR 46 kV 100% I.L.
  Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial.

Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74/ICEA S-93-639

  Electrical Data
 

 

 

 

Continuous operating temperature

 

90º C

Maximum Operating voltage

 

46000 V

Test voltage

 

89 kV ac x 5min

Partial discharge at test voltage

 

< 5 pC



 

 

Download Document:

 
  Data of Cable  


 

Conduct
Size
(AWG / MCM)

Stranded Conductor

Thickness
(mils)

Aprox. weight
(Pounds/kft)

Overall Diam. (inch)

Ampacities

Section (MCM)

Number of Wires

Diameter (inch)

Direct. Burial

In Duct

In Air

Wires

Strand

Insulat.

Jacket

Cu

Al

Cu

Al

Cu

Al

Cu

Al

4/0

212

19

0.106

0.512

445

110

2012

1557

1.797

392

309

330

261

438

344

250

252

37

0.082

0.559

445

110

2216

1678

1.860

429

339

362

287

485

382

300

300

37

0.090

0.612

445

110

2437

1790

1.913

473

375

400

317

540

426

350

350

37

0.097

0.661

445

110

2651

1898

1.963

513

408

434

345

591

468

400

400

37

0.104

0.707

445

110

2861

2002

2.008

550

439

465

372

639

507

500

500

37

0.116

0.789

445

110

3273

2200

2.091

617

495

523

420

728

580

600

600

61

0.099

0.866

445

110

3684

2394

2.167

677

547

575

465

812

650

750

750

61

0.111

0.970

445

110

4288

2672

2.272

756

615

643

525

922

744

800

800

61

0.115

1.000

445

110

4476

2756

2.301

816

664

694

567

995

803

1000

1000

61

0.128

1.118

445

110

5276

3130

2.435

865

715

739

612

1082

885

1250

1250

91

0.117

1.252

445

110

6242

3549

2.569

921

810

754

663

1154

1088

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options :

  1. External cover of PVC
  2. “Sun light Resistant” - “Cable Tray Use”
  3. Screen of Concentric Wires

The provided values are approximated and subject to changes without previous warning.

 