Single Conductor EPR 46 kV 100% I.L. |
 |
| |
Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial. |
|
 |
Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74/ICEA S-93-639
|
|
 |
| |
Electrical Data |
 |
| |
|
|
|
Continuous operating temperature |
|
90º C |
Maximum Operating voltage |
|
46000 V |
Test voltage |
|
89 kV ac x 5min |
Partial discharge at test voltage |
|
< 5 pC |
|
|
|
Download Document:
|
| |
|
| |
Data of Cable |
|
 |
|
Conduct
Size
(AWG / MCM) |
Stranded Conductor |
Thickness
(mils) |
Aprox. weight
(Pounds/kft) |
Overall Diam. (inch) |
Ampacities |
Section (MCM) |
Number of Wires |
Diameter (inch) |
Direct. Burial |
In Duct |
In Air |
Wires |
Strand |
Insulat. |
Jacket |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
4/0 |
212 |
19 |
0.106 |
0.512 |
445 |
110 |
2012 |
1557 |
1.797 |
392 |
309 |
330 |
261 |
438 |
344 |
250 |
252 |
37 |
0.082 |
0.559 |
445 |
110 |
2216 |
1678 |
1.860 |
429 |
339 |
362 |
287 |
485 |
382 |
300 |
300 |
37 |
0.090 |
0.612 |
445 |
110 |
2437 |
1790 |
1.913 |
473 |
375 |
400 |
317 |
540 |
426 |
350 |
350 |
37 |
0.097 |
0.661 |
445 |
110 |
2651 |
1898 |
1.963 |
513 |
408 |
434 |
345 |
591 |
468 |
400 |
400 |
37 |
0.104 |
0.707 |
445 |
110 |
2861 |
2002 |
2.008 |
550 |
439 |
465 |
372 |
639 |
507 |
500 |
500 |
37 |
0.116 |
0.789 |
445 |
110 |
3273 |
2200 |
2.091 |
617 |
495 |
523 |
420 |
728 |
580 |
600 |
600 |
61 |
0.099 |
0.866 |
445 |
110 |
3684 |
2394 |
2.167 |
677 |
547 |
575 |
465 |
812 |
650 |
750 |
750 |
61 |
0.111 |
0.970 |
445 |
110 |
4288 |
2672 |
2.272 |
756 |
615 |
643 |
525 |
922 |
744 |
800 |
800 |
61 |
0.115 |
1.000 |
445 |
110 |
4476 |
2756 |
2.301 |
816 |
664 |
694 |
567 |
995 |
803 |
1000 |
1000 |
61 |
0.128 |
1.118 |
445 |
110 |
5276 |
3130 |
2.435 |
865 |
715 |
739 |
612 |
1082 |
885 |
1250 |
1250 |
91 |
0.117 |
1.252 |
445 |
110 |
6242 |
3549 |
2.569 |
921 |
810 |
754 |
663 |
1154 |
1088 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Options : |
- External cover of PVC
- “Sun light Resistant” - “Cable Tray Use”
- Screen of Concentric Wires
|