Medium voltage power cable / EPR
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  Single Conductor EPR 35 kV 100% I.L.
  Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial.

Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639

  Electrical Data
 

 

 

 

Continuous operating temperature

 

90º C

Maximum Operating voltage

 

35000 V

Test voltage

 

69 kV ac x 5min

Partial discharge at test voltage

 

< 5 pC



 

 

Download Document:

 
  Data of Cable  


 

Conduct
Size
(AWG / MCM)

Stranded Conductor

Thickness
(mils)

Aprox. weight
(Pounds/kft)

Overall Diam. (inch)

Ampacities

Section (MCM)

Number of Wires

Diameter (inch)

Direct. Burial

In Duct

In Air

Wires

Strand

Insulat.

Jacket

Cu

Al

Cu

Al

Cu

Al

Cu

Al

1/0

106

19

0.074

0.362

345

80

1085

859

1.372

275

216

226

177

295

231

2/0

133

19

0.084

0.407

345

80

1214

927

1.417

312

245

256

201

338

265

3/0

168

19

0.094

0.457

345

80

1367

1005

1.467

354

279

290

229

388

305

4/0

212

19

0.106

0.512

345

80

1552

1097

1.522

400

316

329

260

445

350

250

252

37

0.082

0.559

345

80

1717

1179

1.569

438

347

361

286

493

389

300

300

37

0.090

0.612

345

80

1923

1276

1.622

483

383

397

316

549

435

350

350

37

0.097

0.661

345

110

2188

1436

1.732

518

413

431

344

595

473

500

500

37

0.116

0.789

345

110

2802

1729

1.876

622

501

519

419

734

587

750

750

61

0.111

0.970

345

110

3774

2154

2.057

761

622

638

523

929

753

1000

1000

61

0.128

1.118

345

110

4723

2576

2.220

870

722

733

610

1090

896

1250

1250

91

0.117

1.252

345

110

5656

2964

2.354

926

814

759

667

1161

1013

1500

1500

91

0.128

1.370

345

110

6551

3330

2.472

963

972

788

714

1207

1085

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options :

  1. External cover of PVC
  2. “Sun light Resistant” - “Cable Tray Use”
  3. Screen of Concentric Wires

The provided values are approximated and subject to changes without previous warning.

 