Single Conductor EPR 35 kV 100% I.L. |
 |
| |
Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial. |
|
 |
Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639
|
|
 |
| |
Electrical Data |
 |
| |
|
|
|
Continuous operating temperature |
|
90º C |
Maximum Operating voltage |
|
35000 V |
Test voltage |
|
69 kV ac x 5min |
Partial discharge at test voltage |
|
< 5 pC |
|
|
|
Download Document:
|
| |
|
| |
Data of Cable |
|
 |
|
Conduct
Size
(AWG / MCM) |
Stranded Conductor |
Thickness
(mils) |
Aprox. weight
(Pounds/kft) |
Overall Diam. (inch) |
Ampacities |
Section (MCM) |
Number of Wires |
Diameter (inch) |
Direct. Burial |
In Duct |
In Air |
Wires |
Strand |
Insulat. |
Jacket |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
1/0 |
106 |
19 |
0.074 |
0.362 |
345 |
80 |
1085 |
859 |
1.372 |
275 |
216 |
226 |
177 |
295 |
231 |
2/0 |
133 |
19 |
0.084 |
0.407 |
345 |
80 |
1214 |
927 |
1.417 |
312 |
245 |
256 |
201 |
338 |
265 |
3/0 |
168 |
19 |
0.094 |
0.457 |
345 |
80 |
1367 |
1005 |
1.467 |
354 |
279 |
290 |
229 |
388 |
305 |
4/0 |
212 |
19 |
0.106 |
0.512 |
345 |
80 |
1552 |
1097 |
1.522 |
400 |
316 |
329 |
260 |
445 |
350 |
250 |
252 |
37 |
0.082 |
0.559 |
345 |
80 |
1717 |
1179 |
1.569 |
438 |
347 |
361 |
286 |
493 |
389 |
300 |
300 |
37 |
0.090 |
0.612 |
345 |
80 |
1923 |
1276 |
1.622 |
483 |
383 |
397 |
316 |
549 |
435 |
350 |
350 |
37 |
0.097 |
0.661 |
345 |
110 |
2188 |
1436 |
1.732 |
518 |
413 |
431 |
344 |
595 |
473 |
500 |
500 |
37 |
0.116 |
0.789 |
345 |
110 |
2802 |
1729 |
1.876 |
622 |
501 |
519 |
419 |
734 |
587 |
750 |
750 |
61 |
0.111 |
0.970 |
345 |
110 |
3774 |
2154 |
2.057 |
761 |
622 |
638 |
523 |
929 |
753 |
1000 |
1000 |
61 |
0.128 |
1.118 |
345 |
110 |
4723 |
2576 |
2.220 |
870 |
722 |
733 |
610 |
1090 |
896 |
1250 |
1250 |
91 |
0.117 |
1.252 |
345 |
110 |
5656 |
2964 |
2.354 |
926 |
814 |
759 |
667 |
1161 |
1013 |
1500 |
1500 |
91 |
0.128 |
1.370 |
345 |
110 |
6551 |
3330 |
2.472 |
963 |
972 |
788 |
714 |
1207 |
1085 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Options : |
- External cover of PVC
- “Sun light Resistant” - “Cable Tray Use”
- Screen of Concentric Wires
|
The provided values are approximated and subject to changes without previous warning.
|
|