Medium voltage power cable / EPR
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  Single Conductor EPR 25 kV 100% I.L.
  Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial.

Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639

  Electrical Data
 

 

 

 

Continuous operating temperature

 

90º C

Maximum Operating voltage

 

25000 V

Test voltage

 

52 kV ac x 5min

Partial discharge at test voltage

 

< 5 pC



 

 

Download Document:

 
  Data of Cable  


 

Conduct
Size
(AWG / MCM)

Stranded Conductor

Thickness
(mils)

Aprox. weight
(Pounds/kft)

Overall Diam. (inch)

Ampacities

Section (MCM)

Number of Wires

Diameter (inch)

Direct. Burial

In Duct

In Air

Wires

Strand

Insulat.

Jacket

Cu

Al

Cu

Al

Cu

Al

Cu

Al

1

84

19

0.067

0.323

260

80

791

611

1.148

246

193

197

154

257

201

1/0

106

19

0.074

0.362

260

80

886

660

1.187

280

220

224

176

297

233

2/0

133

19

0.084

0.407

260

80

1009

721

1.232

317

249

254

200

340

267

3/0

168

19

0.094

0.457

260

80

1170

808

1.297

359

283

288

228

390

307

4/0

212

19

0.106

0.512

260

80

1347

893

1.352

406

321

326

259

448

353

250

250

37

0.082

0.559

260

80

1506

968

1.400

444

353

358

285

496

393

300

300

37

0.090

0.612

260

80

1705

1058

1.453

489

389

394

315

553

439

350

350

37

0.097

0.661

260

80

1897

1145

1.502

529

423

428

343

606

482

500

500

37

0.116

0.789

260

80

2464

1391

1.630

634

512

515

417

747

600

750

750

61

0.111

0.970

260

110

3497

1881

1.888

766

629

633

521

934

762

1000

1000

61

0.128

1.118

260

110

4424

2277

2.051

874

729

726

607

1096

907

1250

1250

91

0.117

1.252

260

110

5338

2646

2.185

957

957

784

716

1200

1089

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options :

  1. External cover of PVC
  2. “Sun light Resistant” - “Cable Tray Use”
  3. Screen of Concentric Wires

The provided values are approximated and subject to changes without previous warning.

 

  HOME THE COMPANY PRODUCTS TECHNICAL INFORMATION CONTACT US REPRESENTATIVES