Single Conductor EPR 15 kV 100% I.L. |
 |
| |
Underground primary transmition circuits. May be used in wet or dry locations, installed in duct or direct burial. |
|
 |
Standars: AEIC CS8-00 - ICEA S-97-682-2000
NEMA WC -74 / ICEA S-93-639
|
|
 |
| |
Electrical Data |
 |
| |
|
|
|
Continuous operating temperature |
|
90º C |
Maximum Operating voltage |
|
15000 V |
Test voltage 1000 kcmil: |
|
35 kV ac x 5min |
| Test voltage 1000 kcmil: |
|
44 kV ac x 5min |
Partial discharge at test voltage |
|
< 5 pC |
|
|
|
Download Document:
|
| |
|
| |
Data of Cable |
|
 |
|
Conductor
Size
(AWG / MCM) |
Stranded Conductor |
Thickness
(mils) |
Aprox. weight
(Pounds/kft) |
Overall Diam. (inch) |
Ampacities |
Section (MCM) |
Number of Wires |
Diameter (inch) |
Direct. Burial |
In Duct |
In Air |
Wires |
Strand |
Insulat. |
Jacket |
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
2 |
66 |
7 |
0.097 |
0.292 |
175 |
80 |
563 |
421 |
0.945 |
222 |
173 |
172 |
135 |
225 |
176 |
2 |
66 |
19 |
0.059 |
0.287 |
175 |
80 |
559 |
416 |
0.939 |
222 |
173 |
172 |
135 |
225 |
176 |
1 |
84 |
19 |
0.067 |
0.323 |
175 |
80 |
635 |
455 |
0.974 |
253 |
197 |
196 |
153 |
259 |
202 |
1/0 |
106 |
19 |
0.074 |
0.362 |
175 |
80 |
725 |
499 |
1.014 |
285 |
224 |
222 |
175 |
297 |
234 |
2/0 |
133 |
19 |
0.084 |
0.407 |
175 |
80 |
841 |
553 |
1.059 |
323 |
254 |
251 |
198 |
341 |
269 |
3/0 |
168 |
19 |
0.094 |
0.457 |
175 |
80 |
978 |
617 |
1.108 |
365 |
289 |
285 |
226 |
391 |
309 |
4/0 |
212 |
19 |
0.106 |
0.512 |
175 |
80 |
1147 |
693 |
1.163 |
412 |
328 |
323 |
257 |
449 |
356 |
250 |
250 |
37 |
0.082 |
0.559 |
175 |
80 |
1299 |
760 |
1.211 |
451 |
359 |
354 |
283 |
499 |
396 |
300 |
300 |
37 |
0.090 |
0.612 |
175 |
80 |
1506 |
859 |
1.280 |
495 |
396 |
390 |
313 |
556 |
443 |
350 |
350 |
37 |
0.097 |
0.661 |
175 |
80 |
1691 |
939 |
1.329 |
536 |
430 |
423 |
341 |
609 |
487 |
500 |
500 |
37 |
0.116 |
0.789 |
175 |
80 |
2240 |
1167 |
1.457 |
641 |
520 |
510 |
415 |
751 |
607 |
750 |
750 |
61 |
0.111 |
0.970 |
175 |
80 |
3152 |
1536 |
1.638 |
771 |
637 |
625 |
518 |
938 |
770 |
1000 |
1000 |
61 |
0.128 |
1.118 |
175 |
110 |
4142 |
1995 |
1.878 |
878 |
737 |
718 |
604 |
1101 |
918 |
1250 |
1250 |
91 |
0.117 |
1.252 |
220 |
110 |
5192 |
2499 |
2.102 |
923 |
824 |
756 |
675 |
1157 |
1025 |
1500 |
1500 |
91 |
0.128 |
1.370 |
220 |
110 |
6063 |
2841 |
2.220 |
952 |
878 |
780 |
719 |
1193 |
1093 |
1000 |
1000 |
61 |
0.128 |
1.118 |
115 |
110 |
3942 |
1795 |
1.744 |
888 |
751 |
706 |
598 |
1109 |
933 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Options : |
- External cover of PVC
- “Sun light Resistant” - “Cable Tray Use”
- Screen of Concentric Wires
|
The provided values are approximated and subject to changes without previous warning.
|
|