Low voltage power cables / TTU
     
  General information
  Low voltage power cables
  Medium voltage power cables
  Industrial & automotive use
  Control & instrumentation cables
  Comunication, video & sound Cables
  Submarine cable
 
  TTU
  Soft annealed copper solid conductor (14-8 AWG) or stranded class “B” (14 AWG -1000 kcmil), 75°C low density Polyethylene insulation and PVC external Jacket.

Standars: ICEA S-95-658/NEMA WC 70 CIDET00980 COVENIN 541

  APPLICATION
 

For use in building and industrial instalations, especially for underground service lines.
Voltage of operation : 600 V

Download Document:

 
  Data of cable  


 

Size AWG/ kcmil
Construction
Conductor Diameter                  
 (inches)
Thickness (inches)
Aprox. outside diameter
(inches)
Aprox.
Total  weight
(pounds/kft)
Ampacity (A)
N° of wires
Diameter of wires (inches)              
Insulation  (inches)
Jacket      (inches)
14
1
0.064
0.064
0.032
0.018
0.163
21
20
12
1
0.081
0.081
0.032
0.018
0.179
30
25
10
1
0.102
0.102
0.032
0.018
0.201
42
35
8
1
0.129
0.128
0.047
0.018
0.258
68
50
14
7
0.024
0.073
0.032
0.018
0.171
22
20
12
7
0.031
0.092
0.032
0.018
0.191
31
25
10
7
0.039
0.115
0.032
0.018
0.215
45
35
8
7
0.049
0.146
0.047
0.018
0.274
71
50
6
7
0.061
0.183
0.047
0.031
0.340
113
65
4
7
0.077
0.232
0.047
0.031
0.388
168
85
2
7
0.097
0.292
0.047
0.031
0.449
253
115
1/0
19
0.074
0.362
0.057
0.047
0.411
402
150
2/0
19
0.084
0.408
0.057
0.047
0.614
498
175
3/0
19
0.094
0.457
0.057
0.047
0.663
613
200
4/0
19
0.106
0.512
0.057
0.047
0.719
757
230
250
37
0.082
0.559
0.067
0.067
0.827
922
255
300
37
0.090
0.612
0.067
0.067
0.879
1089
285
350
37
0.097
0.661
0.067
0.067
0.929
1253
310
400
37
0.104
0.707
0.067
0.067
0.974
1416
335
500
37
0.116
0.789
0.067
0.067
1.096
1743
380
600
61
0.099
0.866
0.082
0.067
1.163
2092
420
750
61
0.111
0.970
0.082
0.067
1.267
2585
475
1000
61
0.128
1.118
0.082
0.067
1.415
3384
545

Ampacidad not more than three conductors in ductos or directly buried with room temperature of 30°C (86 F) table 310-16 of Nacional Electrical Code . 

Optional :

•  Conductor with greater flexibility (class C) for the calibers of the 14 AWG to 500 MCM

•  External cover of PVC antiflame of low concentration of smoke and low toxic and corrosive gas discharge

(It passes the test of the flame in vertical stairs - UL 1581)

The provided data are approximated and subject to changes without previous warning

 

  HOME THE COMPANY PRODUCTS TECHNICAL INFORMATION CONTACT US REPRESENTATIVES
2005 © Electroconductores, C.A. All rights reserved.